Japan power-frequency magnetic limit for electrical facilities

200 µT (2000 mG) at commercial frequency in the space a person would occupy near transformers, switchgear and power lines, binding since 1 October 2011.

Regulatorygeneral publiccommercial frequency (50/60 Hz)

Last verified 12 August 2026.

Limit value
200 µTRegulatory value — legally enforceable — Ordinance art. 27-2 requires the average flux density in the space equivalent to that occupied by a person to stay at or below 200 µT. Japan adopted this figure from the ICNIRP 2010 revision, which raised the public reference level from 100 µT at 50 Hz and 83 µT at 60 Hz to 200 µT at both.sources: japan-meti-ordinance-52, japan-meti-emf
Quantity
magnetic flux density
Frequency band
commercial frequency (50/60 Hz)
Population
general public
Set by
Japan METI technical standards for electrical facilities (magnetic fields) (Ordinance No. 52 of 1997, art. 27-2 added 31 March 2011, in force 1 October 2011)
Kind
Regulatory — legally enforceable