EMFBase

Poland residential-zoning electric limit at 50 Hz

1000 V/m on land zoned for housing — five times stricter than the 5000 V/m EU/ICNIRP reference level, and a separate stricter tier from the 10,000 V/m that applies in other publicly accessible places.

Regulatorygeneral public50 Hz

Last verified 12 August 2026.

Limit value
1,000 V/mRegulatory value — legally enforceable — Annex, Table 1 (land zoned for housing): E = 1000 V/m, H = 60 A/m, as RMS values. Table 2 allows 10,000 V/m in places merely accessible to the public, so the housing tier is the binding constraint for new transmission lines over residential land.sources: poland-mz-2019-2448
Quantity
electric field strength
Frequency band
50 Hz
Population
general public
Set by
Poland environmental EMF limits (Dz.U. 2019 poz. 2448) (Regulation of 17 December 2019, in force 1 January 2020)
Kind
Regulatory — legally enforceable

Related records

Sources

  1. poland-mz-2019-2448 Rozporządzenie Ministra Zdrowia z dnia 17 grudnia 2019 r. w sprawie dopuszczalnych poziomów pól elektromagnetycznych w środowisku (Dz.U. 2019 poz. 2448) Minister Zdrowia (Poland), Dziennik Ustaw, 2019. regulation, link checked 2026-08-12.

Same record, other formats