Poland residential-zoning electric limit at 50 Hz
1000 V/m on land zoned for housing — five times stricter than the 5000 V/m EU/ICNIRP reference level, and a separate stricter tier from the 10,000 V/m that applies in other publicly accessible places.
Regulatorygeneral public50 Hz
Last verified 12 August 2026.
- Limit value
- 1,000 V/mRegulatory value — legally enforceable — Annex, Table 1 (land zoned for housing): E = 1000 V/m, H = 60 A/m, as RMS values. Table 2 allows 10,000 V/m in places merely accessible to the public, so the housing tier is the binding constraint for new transmission lines over residential land.sources: poland-mz-2019-2448
- Quantity
- electric field strength
- Frequency band
- 50 Hz
- Population
- general public
- Set by
- Poland environmental EMF limits (Dz.U. 2019 poz. 2448) (Regulation of 17 December 2019, in force 1 January 2020)
- Kind
- Regulatory — legally enforceable
Related records
- Poland environmental EMF limits (Dz.U. 2019 poz. 2448)
Poland replaced its 7 V/m environmental RF limit with the EU/ICNIRP reference levels on 1 January 2020, while keeping a stricter 1000 V/m 50 Hz electric-field value for land zoned for housing.
Standards & frameworks
- EU 1999/519/EC public magnetic field reference level, 50 Hz
100 µT (1000 mG) magnetic flux density and 5 kV/m electric field strength at power frequency, the values still in force across the EU.
Exposure limits
Sources
- poland-mz-2019-2448 Rozporządzenie Ministra Zdrowia z dnia 17 grudnia 2019 r. w sprawie dopuszczalnych poziomów pól elektromagnetycznych w środowisku (Dz.U. 2019 poz. 2448) — Minister Zdrowia (Poland), Dziennik Ustaw, 2019. regulation, link checked 2026-08-12.